♣ TR. 용량대비 ACB 선정표 ♣
Trans
Former | 3Φ 전부하전류 | ACB | Capacity | 380V | 440V | 380V | 440V |
| KVA |
| A |
| A |
|
| A |
| | A |
| KVA |
| A |
| A |
|
| A |
|
| A |
| KVA |
| A |
| A |
| | A |
| | A |
| KVA |
| A |
| A |
| | A |
|
| A |
| KVA |
| A |
| A |
|
| A |
| | A |
| KVA |
| A |
| A |
| | A |
|
| A | 400
| KVA | 608 | A | 525 | A | 4P | 600 | A | 3P | 600 | A | 450
| KVA | 684 | A | 591 | A | 4P | 800 | A | 3P | 600 | A | 500
| KVA | 760 | A | 656 | A | 4P | 800 | A | 3P | 800 | A | 550
| KVA | 836 | A | 722 | A | 4P | 1,000 | A | 3P | 800 | A | 600
| KVA | 912 | A | 787 | A | 4P | 1,000 | A | 3P | 800 | A | 650
| KVA | 988 | A | 853 | A | 4P | 1,250 | A | 3P | 1,000 | A | 700
| KVA | 1,064 | A | 919 | A | 4P | 1,250 | A | 3P | 1,000 | A | 750
| KVA | 1,140 | A | 984 | A | 4P | 1,250 | A | 3P | 1,000 | A | 800
| KVA | 1,216 | A | 1,050 | A | 4P | 1,600 | A | 3P | 1,250 | A | 900
| KVA | 1,368 | A | 1,181 | A | 4P | 1,600 | A | 3P | 1,250 | A | 950
| KVA | 1,444 | A | 1,247 | A | 4P | 1,600 | A | 3P | 1,600 | A | 1,000
| KVA | 1,520 | A | 1,312 | A | 4P | 1,600 | A | 3P | 1,600 | A |
ACB 역시 전류 조정 범위 내에서 한 단계 상위의 것을 권합니다. 도움이 되길 바랍니다..