Convenient Data ~ 9
♣ TR. 용량대비 MCCB 선정표 ♣
Trans
Former | 3Φ 전부하전류 | MCCB 선정 | Capacity | 380V | 440V | 380V | 440V | 100 | KVA | 152 | A | 131 | A | 4P | 150 | A | 3P | 150 | A | 150
| KVA | 228 | A | 197 | A | 4P | 250 | A | 3P | 200 | A | 200
| KVA | 304 | A | 262 | A | 4P | 300 | A | 3P | 300 | A | 250
| KVA | 380 | A | 328 | A | 4P | 400 | A | 3P | 350 | A | 300
| KVA | 456 | A | 394 | A | 4P | 500 | A | 3P | 400 | A | 350
| KVA | 532 | A | 459 | A | 4P | 600 | A | 3P | 500 | A | 400
| KVA | 608 | A | 525 | A | 4P | 630 | A | 3P | 600 | A | 450
| KVA | 684 | A | 591 | A | 4P | 700 | A | 3P | 600 | A | 500
| KVA | 760 | A | 656 | A | 4P | 800 | A | 3P | 700 | A | 550
| KVA | 836 | A | 722 | A | 4P | 800 | A | 3P | 800 | A | 600
| KVA | 912 | A | 787 | A | 4P | 1000 | A | 3P | 800 | A | 650
| KVA | 988 | A | 853 | A | 4P | 1000 | A | 3P | 1,000 | A | 700
| KVA | 1,064 | A | 919 | A | 4P | 1200 | A | 3P | 1,000 | A | 750
| KVA | 1,140 | A | 984 | A | 4P | 1200 | A | 3P | 1,000 | A | 800
| KVA | 1,216 | A | 1,050 | A | 4P | 1200 | A | 3P | 1,200 | A |
변압기 용량 500KVA 이상이 되면 주로 ACB를 사용하게 됩니다. 그럼에도 굳이 MCCB(차단기) 조견표를 만든 이유는 ACB는 10년이 지나게 되면 고장이 발생하게 됩니다.
해서 가능 하다면 MCCB를 사용 하는 게 좋겠다는 의미에서 올려봅니다. ACB를 사용하던 MCCB를 사용하던 허용전류 범위에 들면 문제가 되지는 않습니다.
MCCB 는 전류치가 고정 되어 있으므로 부하에 따라 편차가 크므로 가까운 것을 선택하고 전선 규격도 MCCB 용량 이상의 것으로 사용하여야 합니다. MCCB 에도 ACB처럼 TRIP 장치가 있지만 한국전기안전공사에서는 인정하지 않습니다. 도움이 되길 바랍니다.